GSR - трансформатор за трансформатор
  • GSR - трансформатор за трансформатор

Снимките са само с информационна цел. Вижте спецификацията на продукта

please use latin characters

Производител: ELEQ

GSR - трансформатор за трансформатор

GSR bushing-type current transformers

GSR bushing-type current transformers are used for measuring ond protection purposes in generator busbar systems with rated primary currents up to 15000 A. Appropriate sizing of the air gaps between the current transformer housing und busbar system permits applications up to Um - 36kV.

Design safety right through to the core
The GSR bushing-type current transformers consist of toroidal, soft magnetic, highly permeable tape-wound cores, the cores being uniformly wound with copper wire. For larger current strengths the cores come with stabilising windings to counteract the influence of external fields. Depending on the customer's requirements each housing can accommodate up to four cores.

GSR bushing-type current transformers

 

To guarantee the mechanical and electrical resistance of the transformers they are encapsulated in a cast-resin housing with polyurethane.
During the final inspection the current transformers are subjected to a routine test in accordance with the relevant national and international standards such as VDE, IEC BS, ANSI etc..

Installation in any position, almost anywhere

The transformers are furnished with eight M ] 0x40 retaining sockets. Thanks to their sturdy design they can be installed in rooms with high ambient temperatures (in generator busbars, for example).They require no maintenance and can be installed in any position.

Technical data

Rated primary current 50….15000A
Rated secondary current 1A, 5A
Rated burden 50Hz, 60Hz
Rated burden acc. to customers requirement
Accuracy class acc. to customers requirement
Rated insulation level 0.72/3/- kV
Rated short-time thermal current Min. 100 x IN
Standard VDE, IEC, BS, ANSI itp.


Dimensions

GSR bushing-type current transformers - dimensions

Type Maximum primary current
External diameter  Internal diameter Size

GRS 450/290

8000A 450mm 290mm C-F

GRS 540/380

10000A 540mm 380mm C-F

GRS 630/470

10000A 630mm 470mm C-F

GRS 720/560

12500A 720mm 560mm C-F

GRS 810/650

15000A 810mm 650mm C-F

Size
C 150mm
D 200mm
E 250mm
F 300mm

Изпратете запитване

Интересувате ли се от този продукт? Имате ли нужда от допълнителна информация или индивидуални цени?

Свържете се с нас
ПОИСКАЙТЕ ПРОДУКТА close
Благодарим ви, че изпратихте съобщението си. Ние ще отговорим възможно най-скоро.
ПОИСКАЙТЕ ПРОДУКТА close
Преглед

Добави към списъка с желания

Трябва да сте влезли

GSR bushing-type current transformers

GSR bushing-type current transformers are used for measuring ond protection purposes in generator busbar systems with rated primary currents up to 15000 A. Appropriate sizing of the air gaps between the current transformer housing und busbar system permits applications up to Um - 36kV.

Design safety right through to the core
The GSR bushing-type current transformers consist of toroidal, soft magnetic, highly permeable tape-wound cores, the cores being uniformly wound with copper wire. For larger current strengths the cores come with stabilising windings to counteract the influence of external fields. Depending on the customer's requirements each housing can accommodate up to four cores.

GSR bushing-type current transformers

 

To guarantee the mechanical and electrical resistance of the transformers they are encapsulated in a cast-resin housing with polyurethane.
During the final inspection the current transformers are subjected to a routine test in accordance with the relevant national and international standards such as VDE, IEC BS, ANSI etc..

Installation in any position, almost anywhere

The transformers are furnished with eight M ] 0x40 retaining sockets. Thanks to their sturdy design they can be installed in rooms with high ambient temperatures (in generator busbars, for example).They require no maintenance and can be installed in any position.

Technical data

Rated primary current 50….15000A
Rated secondary current 1A, 5A
Rated burden 50Hz, 60Hz
Rated burden acc. to customers requirement
Accuracy class acc. to customers requirement
Rated insulation level 0.72/3/- kV
Rated short-time thermal current Min. 100 x IN
Standard VDE, IEC, BS, ANSI itp.


Dimensions

GSR bushing-type current transformers - dimensions

Type Maximum primary current
External diameter  Internal diameter Size

GRS 450/290

8000A 450mm 290mm C-F

GRS 540/380

10000A 540mm 380mm C-F

GRS 630/470

10000A 630mm 470mm C-F

GRS 720/560

12500A 720mm 560mm C-F

GRS 810/650

15000A 810mm 650mm C-F

Size
C 150mm
D 200mm
E 250mm
F 300mm
Коментари (0)