

Musíte být přihlášen
Category
Montaż urządzeń
Modernizacja induktorów
Urządzenia indukcyjne
asd
Fotografie slouží pouze pro informační účely. Zobrazit specifikaci produktu
please use latin characters
Auxiliary power supply systems are needed to ensure the energy supply for the operation of primary or secondary devices in a station, switchgear or substation. These devices typically include: smart grid electronics, power transformer cooling fans, station battery chargers (DC) and standard wall socket outlets. This double pole voltage transformer generates an output of 230 Volt.
Rated data
Rated primary voltage | 15750V |
---|---|
Rated secondary voltage | 230V |
Rated 50Hz withstand voltage | 50kV |
Rated surge voltage | 95kV |
Rated frequency | 50Hz |
Rated burden | 500VA |
Weight | 47kg |
Secondary terminal protection degree | IP 54 |
Insulation class | E |
Housing | Cast resin |
Standard | EN 61869 – 3:2011 |
Dimensions
Máte zájem o tento produkt? Potřebujete další informace nebo individuální ceny?
musíš být přihlášen
Auxiliary power supply systems are needed to ensure the energy supply for the operation of primary or secondary devices in a station, switchgear or substation. These devices typically include: smart grid electronics, power transformer cooling fans, station battery chargers (DC) and standard wall socket outlets. This double pole voltage transformer generates an output of 230 Volt.
Rated data
Rated primary voltage | 15750V |
---|---|
Rated secondary voltage | 230V |
Rated 50Hz withstand voltage | 50kV |
Rated surge voltage | 95kV |
Rated frequency | 50Hz |
Rated burden | 500VA |
Weight | 47kg |
Secondary terminal protection degree | IP 54 |
Insulation class | E |
Housing | Cast resin |
Standard | EN 61869 – 3:2011 |
Dimensions
Vaše hodnocení nelze odeslat
Nahlásit komentář
Zpráva odeslána
Váš podnět nelze odeslat
Napište svůj názor
Zkontrolovat před odesláním
Vaši recenzi nelze odeslat