Transductores de la serie HOP 500-SB / SP1 y HOP 800 hasta 2000-SB
  • Transductores de la serie HOP 500-SB / SP1 y HOP 800 hasta 2000-SB

Las fotos son solo para fines informativos. Ver especificaciones de producto

please use latin characters

Fabricante: LEM

Transductores de la serie HOP 500-SB / SP1 y HOP 800 hasta 2000-SB

 

HOP 500-SB/SP1

HOP 800-SB

HOP 1000-SB

HOP 1500-SB

HOP 2000-SB

Primary nominal current rmsIPNSK 500A 800A 1000A 1500A 2000A
Primary current measuring range,IPMAX ±1000A ±1600A ±2000A ±3000A ±3000A

Mechanical characteristics
• General tolerance
± 1 mm
• Primary through hole
104 x 40 mm
• Busbar fastening or panel mounting
1 hole ø5,5 i 2 slot 5,5 x 30
• Panel mounting
4 holesy ø3,2
• Distance between holes axes
15 x 150 mm
• Secondary connection
MOLEX 5045-04AG

Remarks
VOUT is positive when IP flows in the direction of the arrow.
The return busbar and primary conductor elbow must be 
located at least at 2.5 x window length more far away from the transducer case.
Temperature of the primary busbar cannot exceed 90°C.
• Parametry dynamiczne są najlepsze gdy szyna pierwotna wypełnia całkowicie okno przetwornika
Dynamic performances are best with a primary busbar completely filling the primary aperture.
 

DImensions [mm]

LEM HOP

Envíe una consulta

¿Estás interesado en este producto? ¿Necesita información adicional o precios individuales?

Contacta con nosotras
SOLICITA EL PRODUCTO close
Gracias por enviar tu mensaje. Responderemos lo antes posible.
SOLICITA EL PRODUCTO close
Vistazo

Añadir a la lista de deseos

Usted debe estar conectado

 

HOP 500-SB/SP1

HOP 800-SB

HOP 1000-SB

HOP 1500-SB

HOP 2000-SB

Primary nominal current rmsIPNSK 500A 800A 1000A 1500A 2000A
Primary current measuring range,IPMAX ±1000A ±1600A ±2000A ±3000A ±3000A

Mechanical characteristics
• General tolerance
± 1 mm
• Primary through hole
104 x 40 mm
• Busbar fastening or panel mounting
1 hole ø5,5 i 2 slot 5,5 x 30
• Panel mounting
4 holesy ø3,2
• Distance between holes axes
15 x 150 mm
• Secondary connection
MOLEX 5045-04AG

Remarks
VOUT is positive when IP flows in the direction of the arrow.
The return busbar and primary conductor elbow must be 
located at least at 2.5 x window length more far away from the transducer case.
Temperature of the primary busbar cannot exceed 90°C.
• Parametry dynamiczne są najlepsze gdy szyna pierwotna wypełnia całkowicie okno przetwornika
Dynamic performances are best with a primary busbar completely filling the primary aperture.
 

DImensions [mm]

LEM HOP