Separador MTL4510-MTL5510 4 canales

The MTLx510 enables four solid-state outputs in the safe area to be controlled by up to four switches or proximity detectors located in a hazardous area. Each pair of output transistors shares a common terminal and can switch +ve or –ve polarity signals. A range of module configurations is available (see Table 1) through the use of selector switches. When proximity detector modes are selected, LFD is enabled and the output switches to OFF if a line fault is detected.


Specificationa


Number of channels 4, configured by switches
Location of switches Zone 0, IIC, T6 hazardous area
Div 1, Group A hazardous location
Hazardous-area inputs Inputs conforming to BS EN60947–5–6:2001 standards for proximity detectors (NAMUR)
Voltage applied to sensor 7 – 9V DC for 1 kOhm +/- 10%
Input/output characteristics Normal phase:
• Outputs closed if input > 2.1mA (< 2kΩ in input circuit)
• Outputs open if input < 1.2mA (> 10kΩ in input circuit)
Hysteresis: 200μA (650Ω) nominal
Line fault detection (LFD) (when selected)* User-selectable via switches on the side of the unit
Open-circuit alarm on if Iin < 50 uA
Open-circuit alarm off if Iin > 250 uA
Short-circuit alarm on if Rin < 100 Ohm
Short-circuit alarm off if Rin > 360 Ohm
Safe-area outputs Floating solid-state outputs compatible with logic circuits
Operating frequency DC to 500Hz
Max. off-state voltage +/- 35V
Max. off-state leakage current +/- 50 uA
Max. on-state resistance 25 Ohm
Max. on-state current +/- 50 mA
LED indicators Green: power indication
Yellow: four: on when output active
Red: LFD indication + faulty channel’s yellow LED flashes
Maximum current consumption 40mA at 24V (with all output channels energised)
Power dissipation within unit 0.96W at 24V, with 10mA loads
Safety description (each channel) Uo=10.5V Io=14mA Po=37mW Um = 253VDC
Modeo/p 1o/p 2o/p 3o/p 4i/p type
0 chA chB chC chD Switch
1 chA rev. chB chC chD
2 chA chB rev. chC chD
3 chA chB chC rev. chD
4 chA chB chC chD rev.
5 chA rev. chB chC rev. chD
6 chA chB rev. chC chD rev.
7 chA rev. chB rev. chC rev. chD rev.
8 chA chB chC chD Prox. detector + LFD
9 chA rev. chB chC chD
10 chA chB rev. chC chD
11 chA chB chC rev. chD
12 chA chB chC chD rev.
13 chA rev. chB chC rev. chD
14 chA chB rev. chC chD rev.
15 chA rev. chB rev. chC rev. chD rev.

See Instruction Manual INM4500 or INM5500 for further mode information.



MTL4510





MTL4510


Envíe una consulta

¿Estás interesado en este producto? ¿Necesita información adicional o precios individuales?

Contacta con nosotras
SOLICITA EL PRODUCTO close
Gracias por enviar tu mensaje. Responderemos lo antes posible.
SOLICITA EL PRODUCTO close
Vistazo

Añadir a la lista de deseos

Usted debe estar conectado

The MTLx510 enables four solid-state outputs in the safe area to be controlled by up to four switches or proximity detectors located in a hazardous area. Each pair of output transistors shares a common terminal and can switch +ve or –ve polarity signals. A range of module configurations is available (see Table 1) through the use of selector switches. When proximity detector modes are selected, LFD is enabled and the output switches to OFF if a line fault is detected.


Specificationa


Number of channels 4, configured by switches
Location of switches Zone 0, IIC, T6 hazardous area
Div 1, Group A hazardous location
Hazardous-area inputs Inputs conforming to BS EN60947–5–6:2001 standards for proximity detectors (NAMUR)
Voltage applied to sensor 7 – 9V DC for 1 kOhm +/- 10%
Input/output characteristics Normal phase:
• Outputs closed if input > 2.1mA (< 2kΩ in input circuit)
• Outputs open if input < 1.2mA (> 10kΩ in input circuit)
Hysteresis: 200μA (650Ω) nominal
Line fault detection (LFD) (when selected)* User-selectable via switches on the side of the unit
Open-circuit alarm on if Iin < 50 uA
Open-circuit alarm off if Iin > 250 uA
Short-circuit alarm on if Rin < 100 Ohm
Short-circuit alarm off if Rin > 360 Ohm
Safe-area outputs Floating solid-state outputs compatible with logic circuits
Operating frequency DC to 500Hz
Max. off-state voltage +/- 35V
Max. off-state leakage current +/- 50 uA
Max. on-state resistance 25 Ohm
Max. on-state current +/- 50 mA
LED indicators Green: power indication
Yellow: four: on when output active
Red: LFD indication + faulty channel’s yellow LED flashes
Maximum current consumption 40mA at 24V (with all output channels energised)
Power dissipation within unit 0.96W at 24V, with 10mA loads
Safety description (each channel) Uo=10.5V Io=14mA Po=37mW Um = 253VDC
Modeo/p 1o/p 2o/p 3o/p 4i/p type
0 chA chB chC chD Switch
1 chA rev. chB chC chD
2 chA chB rev. chC chD
3 chA chB chC rev. chD
4 chA chB chC chD rev.
5 chA rev. chB chC rev. chD
6 chA chB rev. chC chD rev.
7 chA rev. chB rev. chC rev. chD rev.
8 chA chB chC chD Prox. detector + LFD
9 chA rev. chB chC chD
10 chA chB rev. chC chD
11 chA chB chC rev. chD
12 chA chB chC chD rev.
13 chA rev. chB chC rev. chD
14 chA chB rev. chC chD rev.
15 chA rev. chB rev. chC rev. chD rev.