Thermostat miniature Qui 011 / KTS 011
  • Thermostat miniature Qui 011 / KTS 011

Les photos sont à titre informatif uniquement. Voir les spécifications du produit

please use latin characters

Fabricant: STEGO

Thermostat miniature Qui 011 / KTS 011


Wide control range
Small dimensions
Easy to assembly
High contact current
KTO 011: Normally closed thermostat (NC) for heating systems.

KTS 011: Normally open thermostat (NO) for ventilation and cooling systems.

Technical data
Thermostat NC/NO
Temperature range see table
Switching over temperature difference
<8K
Sensor type
Bimetal
Contact type, contact resistance
Fast
<10mOhm
Life time
> 100 000 cycles
Max contact current
AC 250V 10A (resistant load)
AC 120V 15A (resistant load)
AC 250V 2A (inductive load cos phi = 0,6)
AC 120V 2A (inductive load @ cos phi = 0,6)
DC 30 W
EMC
 EN 55014-1-2, EN 61000-3-2, EN 61000-3-3
Terminals
2 pole 2,5 mm2
Mounting
For DIN 35 mm bus , EN 50022
Casing
plastic  UL94V-0, light grey
Dimensions
60 x 33 x 43 mm
Weight
ok. 40 g
Assembly
arbitrary
Operation temperature
-45 do +70 °C (-49 do +158°F)
IP
IP20

 

Catalogue number
Temperature range Article number (NC) Article number (NO) Certificates:
0 do +60 °C 01140.0-00 01141.0-00 VDE
-10 do+50 °C 01142.0-00 01143.0-00 VDE
+20 do +80 °C 01159.0-00 01158.0-00 VDE
32 do 140 °F 01140.9-00 01141.9-00 ULFileNo. E164102
14 do 122 °F 01142.9-00 01143 9-00 ULFileNo.E164102
0 do +60 °C 01146.9-00 01147.9-00 ULFileNo. E164102

Envoyez une demande

Êtes-vous intéressé par ce produit? Avez-vous besoin d'informations supplémentaires ou d'une tarification individuelle?

Nous contacter
DEMANDEZ LE PRODUIT close
Merci d'avoir envoyé votre message. Nous vous répondrons dans les plus brefs délais.
DEMANDEZ LE PRODUIT close
Feuilleter

Ajouter à la liste de souhaits

Vous devez être connecté


Wide control range
Small dimensions
Easy to assembly
High contact current
KTO 011: Normally closed thermostat (NC) for heating systems.

KTS 011: Normally open thermostat (NO) for ventilation and cooling systems.

Technical data
Thermostat NC/NO
Temperature range see table
Switching over temperature difference
<8K
Sensor type
Bimetal
Contact type, contact resistance
Fast
<10mOhm
Life time
> 100 000 cycles
Max contact current
AC 250V 10A (resistant load)
AC 120V 15A (resistant load)
AC 250V 2A (inductive load cos phi = 0,6)
AC 120V 2A (inductive load @ cos phi = 0,6)
DC 30 W
EMC
 EN 55014-1-2, EN 61000-3-2, EN 61000-3-3
Terminals
2 pole 2,5 mm2
Mounting
For DIN 35 mm bus , EN 50022
Casing
plastic  UL94V-0, light grey
Dimensions
60 x 33 x 43 mm
Weight
ok. 40 g
Assembly
arbitrary
Operation temperature
-45 do +70 °C (-49 do +158°F)
IP
IP20

 

Catalogue number
Temperature range Article number (NC) Article number (NO) Certificates:
0 do +60 °C 01140.0-00 01141.0-00 VDE
-10 do+50 °C 01142.0-00 01143.0-00 VDE
+20 do +80 °C 01159.0-00 01158.0-00 VDE
32 do 140 °F 01140.9-00 01141.9-00 ULFileNo. E164102
14 do 122 °F 01142.9-00 01143 9-00 ULFileNo.E164102
0 do +60 °C 01146.9-00 01147.9-00 ULFileNo. E164102
Commentaires (0)
*/ -->