Outdoor Current Transformer – CTH 20

Operating voltage (max.) 17.5 kV - 24 kV
Rated power-frequency withstand voltage (1 min.) 38 kV - 50 kV
Rated impulse test voltage (1,2/50µs) full wave 95 kV - 125 kV
Rated frequency 50 Hz, 60 Hz
Rated primary current 10 A - 4000 A
Primary reconnection 2 x 10 A - 2 x 600 A
Secondary rated current 1 A, 5 A
Maximum Number of Secondary Windings 4
Rated short-time thermal current lth (1s) max. 60 kA (max. 2000 x In)
Rated dynamic current ldyn 2,5 x Ith, max. 120 kA
Short-time load (mechanical) 5000 N
Insulation Class E
Ambient temperature -5… +40°C
Altitude 1000 m
Standard IEC, VDE, ANSI
Weight (approx) 28kg

Other specifications can be produced on demand.

Atsiųskite užklausą

Ar Jūs domina šis produktas? Ar Jums reikia papildomos informacijos ar individualaus pasiūlymo?

Susisiekite su mumis
KLAUSKITE PRODUKTO close
Pranešimas sėkmingai išsiųstas.
KLAUSKITE PRODUKTO close
Naršyti

Pridėti į norų sąrašą

tu turi būti prisijungęs

Outdoor Current Transformer – CTH 20

Operating voltage (max.) 17.5 kV - 24 kV
Rated power-frequency withstand voltage (1 min.) 38 kV - 50 kV
Rated impulse test voltage (1,2/50µs) full wave 95 kV - 125 kV
Rated frequency 50 Hz, 60 Hz
Rated primary current 10 A - 4000 A
Primary reconnection 2 x 10 A - 2 x 600 A
Secondary rated current 1 A, 5 A
Maximum Number of Secondary Windings 4
Rated short-time thermal current lth (1s) max. 60 kA (max. 2000 x In)
Rated dynamic current ldyn 2,5 x Ith, max. 120 kA
Short-time load (mechanical) 5000 N
Insulation Class E
Ambient temperature -5… +40°C
Altitude 1000 m
Standard IEC, VDE, ANSI
Weight (approx) 28kg