The PTC-resistor trip device MSF220SE monitors the winding temperature of machines and equipment. Signals, that can be used as ”early warning" or ”malfunction" (switching-off), are transmitted as soon as the admissible limit temperature is exceeded. Two PTC-circuits can be connected to this unit. The integrated rise-delay time ensures a reliable mains voltage build-up.
Part number:
|
Rated supply voltage Us | AC/DC 90 - 240 V, AC 80 - 264 V, DC 80 - 297 V, < 2 VA AC/DC 24 - 240 V, AC 20 - 264 V, DC 21- 297 V, < 2 VA |
---|---|
Connectable PTC resistors | 2 x 1...6 PTC according to DIN VDE V 0898-1-401 (formerly DIN 44081/82) |
Switching point | <4000 Ω |
Output relay | 2 x 1 change-over-contact (co) |
Type of contact | Type 2 (see general technical information) |
Test conditions | see general technical information |
Rated ambient temperature | -20 ... + 55 ° C |
Dimensions h x w x d | Design S12: 82 x 42 x 121 [mm] |
Attachment | on 35 mm DIN rail according to EN 60 715 or screws M4 (option) |
Protection Housing/Terminals | IP30 / IP20 |
Weight | approx. 210 g |
Ar Jūs domina šis produktas? Ar Jums reikia papildomos informacijos ar individualaus pasiūlymo?
tu turi būti prisijungęs
The PTC-resistor trip device MSF220SE monitors the winding temperature of machines and equipment. Signals, that can be used as ”early warning" or ”malfunction" (switching-off), are transmitted as soon as the admissible limit temperature is exceeded. Two PTC-circuits can be connected to this unit. The integrated rise-delay time ensures a reliable mains voltage build-up.
Part number:
|
Rated supply voltage Us | AC/DC 90 - 240 V, AC 80 - 264 V, DC 80 - 297 V, < 2 VA AC/DC 24 - 240 V, AC 20 - 264 V, DC 21- 297 V, < 2 VA |
---|---|
Connectable PTC resistors | 2 x 1...6 PTC according to DIN VDE V 0898-1-401 (formerly DIN 44081/82) |
Switching point | <4000 Ω |
Output relay | 2 x 1 change-over-contact (co) |
Type of contact | Type 2 (see general technical information) |
Test conditions | see general technical information |
Rated ambient temperature | -20 ... + 55 ° C |
Dimensions h x w x d | Design S12: 82 x 42 x 121 [mm] |
Attachment | on 35 mm DIN rail according to EN 60 715 or screws M4 (option) |
Protection Housing/Terminals | IP30 / IP20 |
Weight | approx. 210 g |