Jūs turite būti prisijungę
Category
Montaż urządzeń
Modernizacja induktorów
Urządzenia indukcyjne
asd
Nuotraukos yra skirtos tik informaciniams tikslams. Peržiūrėkite produkto specifikaciją
please use latin characters
Auxiliary power supply systems are needed to ensure the energy supply for the operation of primary or secondary devices in a station, switchgear or substation. These devices typically include: smart grid electronics, power transformer cooling fans, station battery chargers (DC) and standard wall socket outlets. This double pole voltage transformer generates an output of 230 Volt.
Rated data
Rated primary voltage | 15750V |
---|---|
Rated secondary voltage | 230V |
Rated 50Hz withstand voltage | 50kV |
Rated surge voltage | 95kV |
Rated frequency | 50Hz |
Rated burden | 500VA |
Weight | 47kg |
Secondary terminal protection degree | IP 54 |
Insulation class | E |
Housing | Cast resin |
Standard | EN 61869 – 3:2011 |
Dimensions
Ar Jūs domina šis produktas? Ar Jums reikia papildomos informacijos ar individualaus pasiūlymo?
tu turi būti prisijungęs
Auxiliary power supply systems are needed to ensure the energy supply for the operation of primary or secondary devices in a station, switchgear or substation. These devices typically include: smart grid electronics, power transformer cooling fans, station battery chargers (DC) and standard wall socket outlets. This double pole voltage transformer generates an output of 230 Volt.
Rated data
Rated primary voltage | 15750V |
---|---|
Rated secondary voltage | 230V |
Rated 50Hz withstand voltage | 50kV |
Rated surge voltage | 95kV |
Rated frequency | 50Hz |
Rated burden | 500VA |
Weight | 47kg |
Secondary terminal protection degree | IP 54 |
Insulation class | E |
Housing | Cast resin |
Standard | EN 61869 – 3:2011 |
Dimensions
Jūsų atsiliepimo įvertinimas negali būti išsiųstas
Pranešti apie komentarą
Pranešimas apie atsiliepimą išsiųstas
Jūsų pranešimas apie atsiliepimą neišsiųstas
Parašyti savo atsiliepimą
Atsiliepimas išsiųstas
Jūsų atsiliepimas neišsiųstas