Application
MA16, MB16, MA17, MA19 and MA12 moving-coil meters are intended for measuring d.c. voltage or d.c. current. These meters with built rectifiers can also be used for measuring a.c. voltages and a.c. currents. MA17P, MA19P, MA12P meters with built-in rectifiers are used for measurement of the rectified current or voltage arithmetical mean value and they are such calibrated that they indicate the RMS value at sinusoidal curve shape. The measurement of non-sinusoidal a.c. magnitudes results in additional errors.
MA16, MA17, MA17P, MA19, MA19P, MA12 and MA12P meters are designed for mounting into panels. MB16 meters are adapted for a fast assembly rail mounting (35 mm rail) in compliance with EN 60715 standard MA16, MA17 and MA19 meters are designed for interchangeable dials..
TECHNICAL DATA
Accuracy class | 1.5 |
Internal resistance, voltage drop, current or power consumption | acc. tables 1, 2 and 3 |
Adaptation of the meter measuring range to the range of interchangeable shunts or measuring transducers | by changing of the dial: the dial is simply extracted with a suitable tool and replaced through the upper slot of the case Note: MA12 (144 x 144) meters are not provided for interchangeable dials |
Categories of meter climatic versions
If it is not written otherwise in the order, these meters are intended to use in moderate climatic conditions. Then, we do not place any symbol on the scale. On customers’ request, meters can be adapted to use in conditions of a dry or wet tropical climat. Then, they are marked with the T III symbol.
Requirements concerning safety acc. EN 61010-1 standard:
- maximal phase-earth working voltage | 600 V |
- installation category | III |
- pollution degree | 2 |
- maximal phase-earth working voltage | 600V |
- installation category | III |
- pollution degree | 2 |
- in standard opton: | IP 50 for MA16, MA17, MA17P, MA19, MA19P, MA12, MA12P meters | |
IP 54 (only for MA12 and MA12P meters) | ||
IP 52 (only for MB16 meter) | ||
- with IP 65 front protection grade (on request): | IP 20 terminal protection (with a terminal protective cover) |
Case material | thermoplastic material |
Meter glass material | glass |
Additional setting pointer | On customers request MA17 and MA19 meters can be equiped with an additional, setting red pointer fixed on the glass. |
ACCESSORIES
We deliver with the meter:
- screw holders (for standard options)............. 2 pcs
- screw holders (for IP65 option)..................... 4 pcs
- terminal protection cover............................... 1 pc
- spring holders (only for MA16)...................... 2 pcs
Note: MB16 meters do not have terminal protective cover.
We can also deliver on request, interchangeable shunts of B2, B3,
B4, B5 and B5 types.
Frontal frame dimensions [mm] |
48 x 48*' | 72 x 72 | 96 x 96 | 144x144 | ||||
---|---|---|---|---|---|---|---|---|
Scale length [mm] | 42 | 61 | 95 | 160 | ||||
Weight [kg] | 0,15 | 0,2 | 0,25 | 0,4 | ||||
Type | MA16, MB16 | MA17 | MA19 | MA12 | ||||
Internal resistance 20%, voltage drop or current consumption | ||||||||
Measuring range |
zero on the side of the scale | zero in the middle of the scale | zero on the side of the scale | zero in the middle of the scale | zero on the side of the scale | zero in the middle of the scale | zero on the side of the scale | zero in the middle of the scale |
40 µA | 6,7 kΩ | 6,7 kΩ | ||||||
60 µA | 6,7 kΩ | 2,465 kΩ | ||||||
100 µA | 2,468 kΩ | 1,098 kΩ | 5 kΩ | 2,2 kΩ | 5 kΩ | 2,2 kΩ | 5,8 kΩ | 5,8 kΩ |
150 µA | 2,468 kΩ | 1,098 kΩ | 5 kΩ | 2,2 kΩ | 5 kΩ | 2,2 kΩ | 5,8 kΩ | 2,6 kΩ |
250 µA | 1,097 kΩ | 387 Ω | 2,2 kΩ | 580 Ω | 2,2 kΩ | 580 Ω | 2,6 kΩ | 1,04 kΩ |
400 µA | 387 Ω | 147 Ω | 1,6 kΩ | 225 Ω | 1,6 kΩ | 225 Ω | 1,04 kΩ | 287 Ω |
600 µA | 147 Ω | 70 Ω | 573 Ω | 78,3 Ω | 573 Ω | 78,3 Ω | 753 Ω | 238 Ω |
1 mA | 70 Ω | 69,7 Ω | 225 Ω | 173 Ω | 225 Ω | 173 Ω | 238 Ω | 236 Ω |
1,5 mA | 35 Ω | 14,1 Ω | 76,7 Ω | 17,4 Ω | 76,7 Ω | 17,4 Ω | 69 Ω | 69 Ω |
2,5 mA | 14,1 Ω | 6 Ω | 20,8 Ω | 9,2 Ω | 20,8 Ω | 9,2 Ω | 69 Ω | 13,5 Ω |
4 mA | 6 Ω | 4,5 Ω | 16,5 Ω | 9,3 Ω | 16,5 Ω | 9,3 Ω | 18,2 Ω | 5,2 Ω |
5 mA | 4 Ω | 4,5 Ω | 12,4 Ω | 3,0 Ω | 12,4 Ω | 3,0 Ω | 14,5 Ω | 6,1 Ω |
6 mA | 4 Ω | 4,5 Ω | 9,2 Ω | 3,0 Ω | 9,2 Ω | 3,0 Ω | 14,5 Ω | 3,2 Ω |
10 mA | 2,65 Ω | 2,6 Ω | 3,3 Ω | 2,2 Ω | 3,3 Ω | 2,2 Ω | 6,1 Ω | 2,1 Ω |
15 mA | 2,5 Ω | 2,1 Ω | 2,7 Ω | 2,0 Ω | 2,7 Ω | 2,0 Ω | 3,2 Ω | 2,1 Ω |
20 mA | 2,5 Ω | 2,1 Ω | 2,0 Ω | 1,4 Ω | 2,0 Ω | 1,4 Ω | 2,1 Ω | 1,29 Ω |
25 mA | 60 mV | 2,1 Ω | 1,4 Ω | 2,1 Ω | 1,4 Ω | 2,1 Ω | 1,3 Ω | |
40 mA | 60 mV | 60 mV | 60 mV | 60 mV | ||||
60 mA | 60 mV | 60 mV | 60 mV | 60 mV | ||||
100 mA | 60 mV | 60 mV | 60 mV | 60 mV | ||||
150 mA | 60 mV | 60 mV | 60 mV | 60 mV | ||||
250 mA | 60 mV | 60 mV | 60 mV | 60 mV | ||||
400 mA | 60 mV | 60 mV | 60 mV | 60 mV | ||||
600 mA | 60 mV | 60 mV | 60 mV | 60 mV | ||||
1:00 AM | 60 mV | 60 mV | 60 mV | 60 mV | ||||
1,5 A | 60 mV | 60 mV | 60 mV | 60 mV | ||||
2,5 A | 60 mV | 60 mV | 60 mV | 60 mV | ||||
4:00 AM | 60 mV | 60 mV | 60 mV | 60 mV | ||||
6:00 AM | 60 mV | 60 mV | 60 mV | 60 mV | ||||
10:00 AM | 60 mV | 60 mV | 60 mV | 60 mV | ||||
15 A | 60 mV | 60 mV | 60 mV | 60 mV | ||||
20 A | 60 mV | 60 mV | 60 mV | 60 mV | ||||
25 A | 60 mV | 60 mV | 60 mV | 60 mV | ||||
4...20 mA | 2,44 Ω | 2,7 Ω | 2,7 Ω | |||||
For shunt connection | ||||||||
... A/60 mV | 6 Ω | 6 Ω | 6 Ω | 6 Ω | ||||
...A/150 mV | 30 Ω | 30 Ω | 30 Ω | 30 Ω | ||||
60 mV | 6 Ω | 6 Ω | 6 Ω | 6 Ω | ||||
100 mV | 10 Ω | 10 Ω | 10 Ω | 10 Ω | ||||
150 mV | 30 Ω | 29 Ω | 29 Ω | 35 Ω | ||||
250 mV | 55 Ω | 62 Ω | 62 Ω | 60 Ω | ||||
400 mV | 400 Ω | 260 Ω | 260 Ω | 248 Ω | ||||
600 mV | 604 Ω | 400 Ω | 400 Ω | 386 Ω |
Type | MA16, MB16 | MA17 | MA19 | MA12 | ||||
---|---|---|---|---|---|---|---|---|
Internal resistance 20%, voltage drop or current consumption | ||||||||
Measuring range |
zero on the side of the scale | zero in the middle of the scale | zero on the side of the scale | zero in the middle of the scale | zero on the side of the scale | zero in the middle of the scale | zero on the side of the scale | zero in the middle of the scale |
1 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
1,5 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
2,5 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
4 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
6 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
10 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
15 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
25 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
40 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
60 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
100 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
150 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
250 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
300 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
400 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
500 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
600 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
800 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
1000 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
To co-operate with an external resistor D2 | ||||||||
1500 V | - | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
2500 V | - | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V |
Dc measuring ranges with external shunts
1 A, 1,5 A, 2,5 A , 4 A, 6 A |
1. Measuring movement current considerated when calibrating shunts: B2 - 60 mV – 10 mA B3 - 150 mV – 5 mA 2. Resistance of conductors linking the meter with the shunt: 0.035 W 3. After agreeing with the producer it is possible to offer shunts with following standarized voltage drops: 50 mV, 75 mV, 100 mV 4. Further particulars on shunts are contained in the catalogue: Interchangeable shunts |
Ac measuring ranges
Frontal frame dimensions [mm] |
72 x 72 | 96 x 96 | 144x144 | Notes |
---|---|---|---|---|
Scale length [mm] | 61 | 95 | 160 | |
Weight [kg] | 0,2 | 0,25 | 0,4 | |
Type | MA17P | MA19P | MA12P | |
Measuring range | Drop voltage or power consumption (self-consumption) | |||
400 µA | 1,7 V | 1,7 V | 1,6 V | Rated operational range for frequency 30...1000...10 000 Hz |
600 µA | ||||
1 mA | ||||
1,5 mA | ||||
2,5 mA | ||||
4 mA | ||||
6 mA | ||||
10 mA | ||||
15 mA | ||||
25 mA | ||||
40 mA | ||||
60 mA | ||||
100 mA | ||||
150 mA | ||||
250 mA | ||||
400 mA | ||||
500 mA | ||||
2,5 mA | ||||
600 mA | ||||
1 A | ||||
1A | 5 mW | 5 mW | - |
Rated operational |
1,5 A | 7 mW | 7 mW | - | |
2,5 A | 12 mW | 12 mW | - | |
4 A | 19 mW | 19 mW | - | |
5 A | 21 mW | 21 mW | - | |
6 A | 23 mW | 23 mW | - | |
60 mV | 3 mW | 3 mW | - | |
100 mV | 3 mW | 3 mW | - | |
150 mV | 3 mW | 3 mW | - | |
250 mV | 3 mW | 3 mW | - | |
400 mV | 3 mW | 3 mW | - | |
600 mV | 3 mW | 3 mW | - | |
1 V | 3 mW | 3 mW | - | |
1,5 V | 3 mW | 3 mW | - | |
2,5 V | 1000 W/V | 1000 W/V | 1000 W/V | Rated operational range for frequency 30...1000...10 000 Hz |
4 V | ||||
6 V | ||||
10 V | ||||
15 V | ||||
25 V | ||||
40 V | ||||
60 V | ||||
100 V | ||||
150 V | ||||
250 V | ||||
400 V | ||||
500 V | ||||
600 V |
ORDERING PROCEDURE
In the order one must specify: name and type of meter, measuring range, shunt data if the meter is foressen to co-operate with an interchangeable shunt, working position, kind of climat (only for tropical versions), kind of holders and eventual additional requirements. One must order interchangeable shunts or D2 series resistors. When ordering meters for measuring a.c. current or a.c. voltage, one must add to the meter name „rectifier” - (rectifier meter)
Example of order:
MA16 ammeter, 40 A, c2 30, TIII, screw holders, 0…40 A range
IP54, B2/60 mV- 40 A shunt, IP65.
MA16 – moving-coil meter (48 x 48 mm),
40 A – 40 A range,
c2 30 – working position 30° with relation to horizontal position
(table 4),
TIII – design and materials adapted to specific tropical klimat,
Screw holders – type of holders (screw or spring-holders),
0…40 A – measuring range on the dial,
B2/60 mV/ 40 A – to co-operate with a 40 A shunt of B2 type
IP 54 – protection grade of the casting front
Fig . 1. External dimensions of MB16
Fig. 2. External dimensions of MA16 meters
a) with screw holders
b) with spring holders
Type | a | b | c | d | e | f | g | k |
---|---|---|---|---|---|---|---|---|
mm | ||||||||
MA17, MA17P |
72 | 4 | 68-0,3 | 5 | 45 | 10... 20 | 20,5 | 68+0,7 |
MA19, MA19P |
96 | 4 | 92-0,3 | 5 | 45 | 0. 2 O | 32,5 | 92+0,8 |
MA12, MA12P |
144 | 4,5 | 137,3-05 | 6 | 48 | 10... 20 | 55,5 | 138+10 |
Fig. 3. External dimensions of MA17, MA19 and MA12 meters
![]() |
![]() |
|||||||||||||||
|
Fig. 5. Fixing of meters in the panel
Kod | Working position |
---|---|
0 | c3 α = 90° |
A | c1 α = 0° |
B | c2, α = 15° |
C | c2, α = 30° |
D | c2, α = 45° |
E | c2, α = 60° |
F | c2, α = 75° |
H | c4, α = 105° |
I | c4, α = 120° |
Вы заинтересованы в этом продукте? Вам нужна дополнительная информация или индивидуальные расценки?
Вы должны быть зарегистрированы
Application
MA16, MB16, MA17, MA19 and MA12 moving-coil meters are intended for measuring d.c. voltage or d.c. current. These meters with built rectifiers can also be used for measuring a.c. voltages and a.c. currents. MA17P, MA19P, MA12P meters with built-in rectifiers are used for measurement of the rectified current or voltage arithmetical mean value and they are such calibrated that they indicate the RMS value at sinusoidal curve shape. The measurement of non-sinusoidal a.c. magnitudes results in additional errors.
MA16, MA17, MA17P, MA19, MA19P, MA12 and MA12P meters are designed for mounting into panels. MB16 meters are adapted for a fast assembly rail mounting (35 mm rail) in compliance with EN 60715 standard MA16, MA17 and MA19 meters are designed for interchangeable dials..
TECHNICAL DATA
Accuracy class | 1.5 |
Internal resistance, voltage drop, current or power consumption | acc. tables 1, 2 and 3 |
Adaptation of the meter measuring range to the range of interchangeable shunts or measuring transducers | by changing of the dial: the dial is simply extracted with a suitable tool and replaced through the upper slot of the case Note: MA12 (144 x 144) meters are not provided for interchangeable dials |
Categories of meter climatic versions
If it is not written otherwise in the order, these meters are intended to use in moderate climatic conditions. Then, we do not place any symbol on the scale. On customers’ request, meters can be adapted to use in conditions of a dry or wet tropical climat. Then, they are marked with the T III symbol.
Requirements concerning safety acc. EN 61010-1 standard:
- maximal phase-earth working voltage | 600 V |
- installation category | III |
- pollution degree | 2 |
- maximal phase-earth working voltage | 600V |
- installation category | III |
- pollution degree | 2 |
- in standard opton: | IP 50 for MA16, MA17, MA17P, MA19, MA19P, MA12, MA12P meters | |
IP 54 (only for MA12 and MA12P meters) | ||
IP 52 (only for MB16 meter) | ||
- with IP 65 front protection grade (on request): | IP 20 terminal protection (with a terminal protective cover) |
Case material | thermoplastic material |
Meter glass material | glass |
Additional setting pointer | On customers request MA17 and MA19 meters can be equiped with an additional, setting red pointer fixed on the glass. |
ACCESSORIES
We deliver with the meter:
- screw holders (for standard options)............. 2 pcs
- screw holders (for IP65 option)..................... 4 pcs
- terminal protection cover............................... 1 pc
- spring holders (only for MA16)...................... 2 pcs
Note: MB16 meters do not have terminal protective cover.
We can also deliver on request, interchangeable shunts of B2, B3,
B4, B5 and B5 types.
Frontal frame dimensions [mm] |
48 x 48*' | 72 x 72 | 96 x 96 | 144x144 | ||||
---|---|---|---|---|---|---|---|---|
Scale length [mm] | 42 | 61 | 95 | 160 | ||||
Weight [kg] | 0,15 | 0,2 | 0,25 | 0,4 | ||||
Type | MA16, MB16 | MA17 | MA19 | MA12 | ||||
Internal resistance 20%, voltage drop or current consumption | ||||||||
Measuring range |
zero on the side of the scale | zero in the middle of the scale | zero on the side of the scale | zero in the middle of the scale | zero on the side of the scale | zero in the middle of the scale | zero on the side of the scale | zero in the middle of the scale |
40 µA | 6,7 kΩ | 6,7 kΩ | ||||||
60 µA | 6,7 kΩ | 2,465 kΩ | ||||||
100 µA | 2,468 kΩ | 1,098 kΩ | 5 kΩ | 2,2 kΩ | 5 kΩ | 2,2 kΩ | 5,8 kΩ | 5,8 kΩ |
150 µA | 2,468 kΩ | 1,098 kΩ | 5 kΩ | 2,2 kΩ | 5 kΩ | 2,2 kΩ | 5,8 kΩ | 2,6 kΩ |
250 µA | 1,097 kΩ | 387 Ω | 2,2 kΩ | 580 Ω | 2,2 kΩ | 580 Ω | 2,6 kΩ | 1,04 kΩ |
400 µA | 387 Ω | 147 Ω | 1,6 kΩ | 225 Ω | 1,6 kΩ | 225 Ω | 1,04 kΩ | 287 Ω |
600 µA | 147 Ω | 70 Ω | 573 Ω | 78,3 Ω | 573 Ω | 78,3 Ω | 753 Ω | 238 Ω |
1 mA | 70 Ω | 69,7 Ω | 225 Ω | 173 Ω | 225 Ω | 173 Ω | 238 Ω | 236 Ω |
1,5 mA | 35 Ω | 14,1 Ω | 76,7 Ω | 17,4 Ω | 76,7 Ω | 17,4 Ω | 69 Ω | 69 Ω |
2,5 mA | 14,1 Ω | 6 Ω | 20,8 Ω | 9,2 Ω | 20,8 Ω | 9,2 Ω | 69 Ω | 13,5 Ω |
4 mA | 6 Ω | 4,5 Ω | 16,5 Ω | 9,3 Ω | 16,5 Ω | 9,3 Ω | 18,2 Ω | 5,2 Ω |
5 mA | 4 Ω | 4,5 Ω | 12,4 Ω | 3,0 Ω | 12,4 Ω | 3,0 Ω | 14,5 Ω | 6,1 Ω |
6 mA | 4 Ω | 4,5 Ω | 9,2 Ω | 3,0 Ω | 9,2 Ω | 3,0 Ω | 14,5 Ω | 3,2 Ω |
10 mA | 2,65 Ω | 2,6 Ω | 3,3 Ω | 2,2 Ω | 3,3 Ω | 2,2 Ω | 6,1 Ω | 2,1 Ω |
15 mA | 2,5 Ω | 2,1 Ω | 2,7 Ω | 2,0 Ω | 2,7 Ω | 2,0 Ω | 3,2 Ω | 2,1 Ω |
20 mA | 2,5 Ω | 2,1 Ω | 2,0 Ω | 1,4 Ω | 2,0 Ω | 1,4 Ω | 2,1 Ω | 1,29 Ω |
25 mA | 60 mV | 2,1 Ω | 1,4 Ω | 2,1 Ω | 1,4 Ω | 2,1 Ω | 1,3 Ω | |
40 mA | 60 mV | 60 mV | 60 mV | 60 mV | ||||
60 mA | 60 mV | 60 mV | 60 mV | 60 mV | ||||
100 mA | 60 mV | 60 mV | 60 mV | 60 mV | ||||
150 mA | 60 mV | 60 mV | 60 mV | 60 mV | ||||
250 mA | 60 mV | 60 mV | 60 mV | 60 mV | ||||
400 mA | 60 mV | 60 mV | 60 mV | 60 mV | ||||
600 mA | 60 mV | 60 mV | 60 mV | 60 mV | ||||
1:00 AM | 60 mV | 60 mV | 60 mV | 60 mV | ||||
1,5 A | 60 mV | 60 mV | 60 mV | 60 mV | ||||
2,5 A | 60 mV | 60 mV | 60 mV | 60 mV | ||||
4:00 AM | 60 mV | 60 mV | 60 mV | 60 mV | ||||
6:00 AM | 60 mV | 60 mV | 60 mV | 60 mV | ||||
10:00 AM | 60 mV | 60 mV | 60 mV | 60 mV | ||||
15 A | 60 mV | 60 mV | 60 mV | 60 mV | ||||
20 A | 60 mV | 60 mV | 60 mV | 60 mV | ||||
25 A | 60 mV | 60 mV | 60 mV | 60 mV | ||||
4...20 mA | 2,44 Ω | 2,7 Ω | 2,7 Ω | |||||
For shunt connection | ||||||||
... A/60 mV | 6 Ω | 6 Ω | 6 Ω | 6 Ω | ||||
...A/150 mV | 30 Ω | 30 Ω | 30 Ω | 30 Ω | ||||
60 mV | 6 Ω | 6 Ω | 6 Ω | 6 Ω | ||||
100 mV | 10 Ω | 10 Ω | 10 Ω | 10 Ω | ||||
150 mV | 30 Ω | 29 Ω | 29 Ω | 35 Ω | ||||
250 mV | 55 Ω | 62 Ω | 62 Ω | 60 Ω | ||||
400 mV | 400 Ω | 260 Ω | 260 Ω | 248 Ω | ||||
600 mV | 604 Ω | 400 Ω | 400 Ω | 386 Ω |
Type | MA16, MB16 | MA17 | MA19 | MA12 | ||||
---|---|---|---|---|---|---|---|---|
Internal resistance 20%, voltage drop or current consumption | ||||||||
Measuring range |
zero on the side of the scale | zero in the middle of the scale | zero on the side of the scale | zero in the middle of the scale | zero on the side of the scale | zero in the middle of the scale | zero on the side of the scale | zero in the middle of the scale |
1 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
1,5 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
2,5 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
4 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
6 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
10 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
15 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
25 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
40 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
60 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
100 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
150 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
250 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
300 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
400 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
500 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
600 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
800 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
1000 V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
To co-operate with an external resistor D2 | ||||||||
1500 V | - | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V | ||||
2500 V | - | 1000 Ω/V | 1000 Ω/V | 1000 Ω/V |
Dc measuring ranges with external shunts
1 A, 1,5 A, 2,5 A , 4 A, 6 A |
1. Measuring movement current considerated when calibrating shunts: B2 - 60 mV – 10 mA B3 - 150 mV – 5 mA 2. Resistance of conductors linking the meter with the shunt: 0.035 W 3. After agreeing with the producer it is possible to offer shunts with following standarized voltage drops: 50 mV, 75 mV, 100 mV 4. Further particulars on shunts are contained in the catalogue: Interchangeable shunts |
Ac measuring ranges
Frontal frame dimensions [mm] |
72 x 72 | 96 x 96 | 144x144 | Notes |
---|---|---|---|---|
Scale length [mm] | 61 | 95 | 160 | |
Weight [kg] | 0,2 | 0,25 | 0,4 | |
Type | MA17P | MA19P | MA12P | |
Measuring range | Drop voltage or power consumption (self-consumption) | |||
400 µA | 1,7 V | 1,7 V | 1,6 V | Rated operational range for frequency 30...1000...10 000 Hz |
600 µA | ||||
1 mA | ||||
1,5 mA | ||||
2,5 mA | ||||
4 mA | ||||
6 mA | ||||
10 mA | ||||
15 mA | ||||
25 mA | ||||
40 mA | ||||
60 mA | ||||
100 mA | ||||
150 mA | ||||
250 mA | ||||
400 mA | ||||
500 mA | ||||
2,5 mA | ||||
600 mA | ||||
1 A | ||||
1A | 5 mW | 5 mW | - |
Rated operational |
1,5 A | 7 mW | 7 mW | - | |
2,5 A | 12 mW | 12 mW | - | |
4 A | 19 mW | 19 mW | - | |
5 A | 21 mW | 21 mW | - | |
6 A | 23 mW | 23 mW | - | |
60 mV | 3 mW | 3 mW | - | |
100 mV | 3 mW | 3 mW | - | |
150 mV | 3 mW | 3 mW | - | |
250 mV | 3 mW | 3 mW | - | |
400 mV | 3 mW | 3 mW | - | |
600 mV | 3 mW | 3 mW | - | |
1 V | 3 mW | 3 mW | - | |
1,5 V | 3 mW | 3 mW | - | |
2,5 V | 1000 W/V | 1000 W/V | 1000 W/V | Rated operational range for frequency 30...1000...10 000 Hz |
4 V | ||||
6 V | ||||
10 V | ||||
15 V | ||||
25 V | ||||
40 V | ||||
60 V | ||||
100 V | ||||
150 V | ||||
250 V | ||||
400 V | ||||
500 V | ||||
600 V |
ORDERING PROCEDURE
In the order one must specify: name and type of meter, measuring range, shunt data if the meter is foressen to co-operate with an interchangeable shunt, working position, kind of climat (only for tropical versions), kind of holders and eventual additional requirements. One must order interchangeable shunts or D2 series resistors. When ordering meters for measuring a.c. current or a.c. voltage, one must add to the meter name „rectifier” - (rectifier meter)
Example of order:
MA16 ammeter, 40 A, c2 30, TIII, screw holders, 0…40 A range
IP54, B2/60 mV- 40 A shunt, IP65.
MA16 – moving-coil meter (48 x 48 mm),
40 A – 40 A range,
c2 30 – working position 30° with relation to horizontal position
(table 4),
TIII – design and materials adapted to specific tropical klimat,
Screw holders – type of holders (screw or spring-holders),
0…40 A – measuring range on the dial,
B2/60 mV/ 40 A – to co-operate with a 40 A shunt of B2 type
IP 54 – protection grade of the casting front
Fig . 1. External dimensions of MB16
Fig. 2. External dimensions of MA16 meters
a) with screw holders
b) with spring holders
Type | a | b | c | d | e | f | g | k |
---|---|---|---|---|---|---|---|---|
mm | ||||||||
MA17, MA17P |
72 | 4 | 68-0,3 | 5 | 45 | 10... 20 | 20,5 | 68+0,7 |
MA19, MA19P |
96 | 4 | 92-0,3 | 5 | 45 | 0. 2 O | 32,5 | 92+0,8 |
MA12, MA12P |
144 | 4,5 | 137,3-05 | 6 | 48 | 10... 20 | 55,5 | 138+10 |
Fig. 3. External dimensions of MA17, MA19 and MA12 meters
![]() |
![]() |
|||||||||||||||
|
Fig. 5. Fixing of meters in the panel
Kod | Working position |
---|---|
0 | c3 α = 90° |
A | c1 α = 0° |
B | c2, α = 15° |
C | c2, α = 30° |
D | c2, α = 45° |
E | c2, α = 60° |
F | c2, α = 75° |
H | c4, α = 105° |
I | c4, α = 120° |
Не удаётся отправить вашу оценку отзыва
Пожаловаться на комментарий
Жалоба отправлена
Не удаётся отправить вашу жалобу
Оставьте свой отзыв
Отзыв отправлен
Не удаётся отправить отзыв